;****************************************************** ; Device Data Base for AJ95TB32-16DT ; Date: 30.07.1997 ; File Name: AJ95F033.GSD ; Revision: M. Heitmann ;****************************************************** ; #Profibus_DP GSD_Revision = 2 ; Vendor_Name = "MITSUBISHI ELECTRIC CORPORATION" Model_Name = "Mitsu. - AJ95TB32-16DT 8DI/8DO" Revision = "MEU-GER V1.0" Ident_Number = 0xF033 Protocol_Ident = 0 Station_Type = 0 FMS_supp = 0 Hardware_Release = "A" Software_Release = "none" ; 9.6_supp = 1 19.2_supp = 1 93.75_supp = 1 187.5_supp = 1 500_supp = 1 1.5M_supp = 1 3M_supp = 1 6M_supp = 1 12M_supp = 1 MaxTsdr_9.6 = 60 MaxTsdr_19.2 = 60 MaxTsdr_93.75 = 60 MaxTsdr_187.5 = 60 MaxTsdr_500 = 100 MaxTsdr_1.5M = 150 MaxTsdr_3M = 250 MaxTsdr_6M = 450 MaxTsdr_12M = 800 ; Redundancy = 0 Repeater_Ctrl_Sig = 1 24V_Pins = 0 ;Implementation_Type = "implementation type" ;Bitmap_Device = "bmpdev.dib" ;Bitmap_Diag = "bmpdia.dib" ;Bitmap_SF = "bmpsf.dib" ; ; Slave specific Values ; Freeze_Mode_supp = 1 Sync_Mode_supp = 1 Auto_Baud_supp = 1 Set_Slave_Add_supp = 0 User_Prm_Data_Len = 05 User_Prm_Data = 0x00,0x00,0x00,0x00,0x00 Min_Slave_Intervall = 1 ; Modular_Station = 0 ;Modul_Offset = 255 ; Fail_Safe = 0 Slave_Family = 3 Max_Diag_Data_Len = 13 Unit_Diag_Bit(0) = "SHORT CIRCUIT ON I/O" Unit_Diag_Bit(1) = "POWER SUPPLY FAILURE" ; ; Module = "aj95tb32-16dt" 0x20,0x10 EndModule